Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 609
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00129
 
C00129
C00130
C00131
C00133
C00134
Parameter | Name:
C00129 | Brake resistance value
Data type: UNSIGNED_16
Index: 24446
d
 = 5F7E
h
As of version 02.00.00
Resistance value of the connected brake resistor
 • The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range (min. value | unit | max. value) Lenze setting
0.0 Ohm 500.0 39.0 Ohm
; Read access ; Write access  CINH  PLC STOP  No transfer  COM ; MOT Scaling factor: 10
Parameter | Name:
C00130 | Rated brake resistor power
Data type: UNSIGNED_16
Index: 24445
d
 = 5F7D
h
As of version 02.00.00
Rated power of the connected brake resistor
 • The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range (min. value | unit | max. value) Lenze setting
0 w 65535 100 W
; Read access ; Write access  CINH  PLC STOP  No transfer  COM ; MOT Scaling factor: 1
Parameter | Name:
C00131 | Thermal capacity of brake resistor
Data type: UNSIGNED_16
Index: 24444
d
 = 5F7C
h
Thermal capacity of the connected brake resistor
 • The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range (min. value | unit | max. value) Lenze setting
0.0 kWs 6553.5 10.0 kWs
; Read access ; Write access  CINH  PLC STOP  No transfer  COM ; MOT Scaling factor: 10
Parameter | Name:
C00133 | Brake resistor utilisation
Data type: UNSIGNED_16
Index: 24442
d
 = 5F7A
h
Display of the utilisation of the connected brake resistor
Display range (min. value | unit | max. value)
0 % 65535
; Read access  Write access  CINH  PLC STOP  No transfer  COM ; MOT Scaling factor: 1
Parameter | Name:
C00134 | Ramp rounding main setpoint
Data type: UNSIGNED_8
Index: 24441
d
 = 5F79
h
Configuration of the ramp rounding for the main setpoint
Selection list (Lenze setting printed in bold) Info
0Off Ramp rounding deactivated
1 PT1 behaviour Ramp rounding with PT1 behaviour
 • The corresponding S-ramp time must be set in 
C00182
.
; Read access ; Write access  CINH  PLC STOP  No transfer  COM  MOT Scaling factor: 1