8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00581
C00581
C00582
C00585
Parameter | Name:
C00581 | Resp. LS_SetError_x
Data type: UNSIGNED_8
Index: 23994
d
= 5DBA
h
Selection of the error responses for application error messages
• An application error message is tripped by a FALSE/TRUE edge at the binary inputs bSetError1...4.
Selection list
0 No Reaction
1Fault
2Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes Lenze setting Info
C00581/1 0: No Reaction LS_SetError_1
: Resp. bSetError1
C00581/2 0: No Reaction LS_SetError_1
: Resp. bSetError2
C00581/3 0: No Reaction LS_SetError_1
: Resp. bSetError3
C00581/4 0: No Reaction LS_SetError_1
: Resp. bSetError4
C00581/5 0: No Reaction LS_SetError_2
: Resp. bSetError1
C00581/6 0: No Reaction LS_SetError_2
: Resp. bSetError2
C00581/7 0: No Reaction LS_SetError_2
: Resp. bSetError3
C00581/8 0: No Reaction LS_SetError_2
: Resp. bSetError4
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00582 | Resp. to heatsink temp. > shutdown temp. -5°C
Data type: UNSIGNED_8
Index: 23993
d
= 5DB9
h
Response when the heatsink temperature has reached the shutdown temperature threshold.
Selection list (Lenze setting printed in bold)
0No Reaction
1Fault
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00585 | Resp. to motor overtemp. PTC
Data type: UNSIGNED_8
Index: 23990
d
= 5DB6
h
Response to motor overtemperature
• The motor temperature is measured by means of a PTC thermistor at terminal X106.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1