EasyManua.ls Logo

Lenze E84AVHC Series - 10.2.2 Setting the baud rate; 10.2.3 Setting the node address

Lenze E84AVHC Series
1118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8400 HighLine | Parameter setting & configuration
System bus "CAN on board"
Possible settings via DIP switch
506 L Firmware 05.00 - DMS 4.2 EN - 02/2010
10.2.2 Setting the baud rate
The baud rate can be set via code C00351
or with the DIP switches a to d:
10.2.3 Setting the node address
The node address can be set via code C00350
or with the DIP switches 1 to 64.
The labelling on the housing corresponds to the values of the individual DIP switches
for determining the node address.
Valid address range: 1 to 63
Example: Setting of the node address 23
DIP switch position Baud rate
d c b a
OFF OFF ON ON 50 kbps
OFF OFF ON OFF 125 kbps
OFF OFF OFF ON 250 kbps
OFF OFF OFF OFF 500 kbps
ON ON ON OFF 800 kbps
(Setting is only effective from "HighLine" version
OFF ON OFF OFF 1000 kbps
(Setting is only effective from "HighLine" version
Note!
The addresses of the nodes must differ from each other.
All DIP switches (a ... d, 1 ... 64) = OFF (Lenze setting):
At switching on, the settings under code C00350
(node address) and
C00351
(baud rate) will become active.
DIP switch 64 32 16 8 4 2 1
Switch position OFF OFF ON OFF ON ON ON
Value 0 0
16 0 4 2 1
Node address = Sum of the values = 16 + 4 + 2 + 1 = 23
efesotomasyon.com - Lenze