8400 HighLine | Parameter setting & configuration
Diagnostics & error management
Error messages of the operating system
OH4: Heatsink temp. > shutdown temp. -5°C [xx.0119.00000]
OH1: Heatsink overtemperature [xx.0119.00001]
OH3: OH3: Motor temperature (X106) triggered [xx.0119.00015]
OC5: Ixt overload [xx.0119.00050]
OT1: Maximum torque reached [xx.0123.00001]
Response (Lenze setting printed in bold) Setting: C00582 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
The heatsink temperature now only differs by 5 °C from
the shutdown temperature of the motor.
Prevent further heating, i.e. reduce motor load or set
controller inhibit so that the heatsink can cool down
again.
Response (Lenze setting printed in bold)
None : Fault Trouble TroubleQuickstop Warning WarningLocked Information
Cause Remedy
The heatsink temperature is higher than the fixed limit
temperature (90 ° C).
Maybe the ambient temperature of the controller is too
high or the fan or its ventilation slots are dirty.
Check control cabinet temperature.
Clean filter.
Clean controller.
If required, clean or replace the fan.
Provide for sufficient cooling of the device.
Response (Lenze setting printed in bold) Setting: C00585 (; Adjustable response)
; None : Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
The motor temperature monitoring function at the plug
connector X106, terminal T1 /T2, has tripped.
Possible causes:
The motor is overheated so that the thermal contact
integrated into the motor has been switched.
An open circuit or a loose contact at the connections
mentioned above has occurred.
Check motor temperature monitoring.
Provide for sufficient cooling of the motor.
Check terminals for open circuit or loose contact.
Response (Lenze setting printed in bold) Setting: C00604 (; Adjustable response)
; None ; Fault Trouble TroubleQuickstop : Warning WarningLocked Information
Cause Remedy
The Ixt overload check has tripped.
Possible causes:
Wrong dimensioning of the device with regard to its
motor load.
Load cycles are not complied with.
Check and, if required, correct dimensioning of the
device and the motor load with regard to technical
data.
Reduce motor load cycles (observe load cycles
according to documentation).
Response (Lenze setting printed in bold) Setting: C00608 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
The device indicates that the maximally possible torque
at the motor shaft has been reached.
C00057
displays the current torque.
Reduce motor load.