Firmware 05.00 - DMS 4.2 EN - 02/2010 L 821
8400 HighLine | Parameter setting & configuration
Working with the FB Editor
Basics
13.1.1 Basic components of a drive solution
A drive solution consists of the following basic components:
Signal sources (for control and setpoint signals)
Signal flow of the technology application
Signal outputs (for status and actual value signals)
[13-1] Basic components of a drive solution
Regarding the 8400 device series, these three components are available for the FB
interconnection and classified as follows:
Further information on the individual modules can be obtained from the following
subchapters!
Note!
With the "StateLine" version, the interconnection shown in the application level
cannot be edited.
STOP
M
0
1
n
t
è
ç
...............
..............
Signal
inputs
Setpoint
generator
PID
Process
controller
Drive
control
Motor
control
Signal
outputs
Actuating drive-speed
.................
Motion
Module type Name Task Example
Function block L_name General function block for free
interconnection (only HighLine)
L_Compare_1
L_PCTRL_1
System block LS_name Signal interface to inverter-internal
functions
LS_DigitalInput
LS_AnalogOutput
Port block LP_name Process data communication via a
fieldbus using a communication module
Process data communication via CAN on
board
LP_CanIn1/-Out1
LP_CanIn2/-Out2
LP_CanIn3/-Out3
LP_MciIn/ -Out
Application block LA_name Block for a technology application LA_NCtrl