8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00103
606 L Firmware 05.00 - DMS 4.2 EN - 02/2010
C00103
C00105
C00106
C00107
Parameter | Name:
C00103 | Add. deceleration time x
Data type: UNSIGNED_32
Index: 24472
d
= 5F98
h
FB L_NSet_1: Additional deceleration times for the main setpoint
The additional deceleration times set here can be selected via the binary inputs bTI1 ... bTI8 of the L_NSet_1
FB.
Setting range (min. value | unit | max. value)
0.000 s 999.999
Subcodes Lenze setting Info
C00103/1 0.000 s Additional deceleration time 1 ... 15
C00103/...
C00103/15
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00105 | Deceleration time - quick stop
Data type: UNSIGNED_32
Index: 24470
d
= 5F96
h
The set deceleration time determines the ramp slope at quick stop
Setting range (min. value | unit | max. value) Lenze setting
0.000 s 999.900 2.000 s
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00106 | Auto-DCB: Hold time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
Hold time of the automatic DC injection brake
The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in C00019
.
Setting range (min. value | unit | max. value) Lenze setting
0.000 s 999.000 0.500 s
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C00107 | DCB: Hold time
Data type: UNSIGNED_32
Index: 24468
d
= 5F94
h
Maximum hold time of the manual DC injection brake
In order not to overload the motor thermally, a time for automatic switch-off of the DC injection brake can be set
here.
Setting range (min. value | unit | max. value) Lenze setting
0.000 s 999.000 999.000 s
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000