Firmware 05.00 - DMS 4.2 EN - 02/2010 L 87
8400 HighLine | Parameter setting & configuration
Device control (DCTRL)
Automatic restart after mains connection/fault...
4.3 Automatic restart after mains connection/fault...
.../error/undervoltage
In C00142
, the starting performance of the controller after mains connection,
undervoltage, as well as a "Trouble
" or a "Fault" reset can be parameterised individually:
Auto-start option (C00142) Lenze setting
Bit 0 Inhibit at power-on 1 Inhibit is active
Bit 1 Inhibit at trouble 0 Inhibit is not active
Bit 2 Inhibit at fault 0 Inhibit is not active
Bit 3 Inhibit at undervoltage 1 Inhibit is active
Bit 4 ... 7 Reserved 0
Note!
In the Lenze setting , automatic restart after mains connection or undervoltage
is inhibited.
Danger!
If the "Inhibit at power-on" auto-start option has been deactivated in C00142
(bit 0 = 0), a direct change from the "ReadyToSwitchON
" state to the
"SwitchedON
" state is performed after mains connection!