8400 HighLine | Parameter setting & configuration
Device control (DCTRL)
Automatic restart after mains connection/fault...
88 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
 
"Inhibit at power-on" auto-start option
 If the "Inhibit at power-on" auto-start option has been activated in C00142
 (Lenze 
setting), explicit deactivation of the controller inhibit is always required after mains 
connection for the controller to change from the "ReadyToSwitchON
" state to the 
"SwitchedON
" state:
[4-3] State changes if the "Inhibit at power-on" auto-start option has been activated (C00142: bit 0 = 1)
 The illustration below shows the state changes if auto-restart after mains connection 
has been enabled (C00142
: bit 0 = 0), depending on the controller inhibit:
[4-4] State changes if the "Inhibit at power-on" auto-start option has been deactivated (C00142: bit 0 = 0)
Controller pulses are inhibited
Controller pulses are enabled
n
o
With controller inhibit during power-up
Without controller inhibit during power-up
RFR
01
RFR
RFR
RFR
t
t
Init SwitchedOn OperationEnabledReadyToSwitchOn
Init SwitchedOn OperationEnabledReadyToSwitchOn
Controller pulses are inhibited
Controller pulses are enabled
n
o
With controller inhibit during power-up
Without controller inhibit during power-up
RFR
01
RFR
RFR
RFR
t
t
Init SwitchedOn OperationEnabledReadyToSwitchOn
Init SwitchedOn OperationEnabledReadyToSwitchOn