EasyManua.ls Logo

Lenze E84AVHC Series - C00231 | L_PCTRL_1: Operating range; C00233 | L_PCTRL_1: Root function; C00234 | Oscillation damping influence; C00235 | Filter time - oscill. damping

Lenze E84AVHC Series
1118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00231
630 L Firmware 05.00 - DMS 4.2 EN - 02/2010
C00231
C00233
C00234
C00235
C00236
Parameter | Name:
C00231 | L_PCTRL_1: Operating range
Data type: INTEGER_16
Index: 24344
d
= 5F18
h
FB L_PCTRL_1: Operating range for the PID process controller
Setting range (min. value | unit | max. value)
0.00 % 199.99
Subcodes Lenze setting Info
C00231/1 199.99 % L_PCTRL_1
: Pos. maximum
C00231/2 0.00 % L_PCTRL_1
: Pos. minimum
C00231/3 0.00 % L_PCTRL_1
: Neg. minimum
C00231/4 199.99 % L_PCTRL_1
: Neg. maximum
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00233 | L_PCTRL_1: Root function
Data type: UNSIGNED_8
Index: 24342
d
= 5F16
h
FB L_PCTRL_1: Use of the root function at the actual value input
Selection list (Lenze setting printed in bold) Info
0Off Root function inactive
The actual value nAct_a is not changed for further
processing.
1 On Root function active
The square root of the actual value nAct_a is taken for
further processing.
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00234 | Oscillation damping influence
Data type: UNSIGNED_16
Index: 24341
d
= 5F15
h
Oscillation damping
Setting range (min. value | unit | max. value) Lenze setting
0.00 % 250.00 5.00 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00235 | Filter time - oscill. damping
Data type: UNSIGNED_8
Index: 24340
d
= 5F14
h
Oscillation damping
Setting range (min. value | unit | max. value) Lenze setting
2 ms 250 32 ms
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00236 | Oscill. damping - field weaken.
Data type: UNSIGNED_8
Index: 24339
d
= 5F13
h
Oscillation damping for idling machines
Oscillation damping
Setting range (min. value | unit | max. value) Lenze setting
04014
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
efesotomasyon.com - Lenze