Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 389
8400 HighLine | Parameter setting & configuration
Basic drive functions (MCK)
Basic settings
8.4.2 Min/Max speed
You can initially limit the speed setpoint by means of the following parameters:
In the »Engineer», you can set the initial limit by means of the dialog box Min/Max speed.
Open the Min/max speed dialog box by opening the Application Parameters tab and
clicking on the following button on the dialog level Overview Signal flow:
8.4.3 Limit position monitoring
8.4.3.1 Software limit positions
The parameterisable limit positions are used by the software to limit the traversing range.
The positive software limit position is set in C01229/1
and the negative software limit
position is set in C01229/2
.
Parameter Info Lenze setting
Value Unit
C02610/2 MCK: Setpoint - ramp time synchronisation 2.000 s
C02611/1
MCK: Pos. max. speed 199.99 %
C02611/2
MCK: Pos. min. speed 0.00 %
C02611/3
MCK: Neg. min. speed 0.00 %
C02611/4
MCK: Neg. max. speed 199.99 %
Stop!
The software limit positions are only evaluated and monitoring if the drive
knows the home position and the software limit positions for the respective
operating mode have been activated.
• For the "manual jogging" operating mode, travel range monitoring is
switched off by means of parameterisable software limit positions in the
Lenze setting of C01230
.
• In the "Homing
" and "Positioning" operating modes, the travel range
monitoring is generally switched-on.
Parameter Info Lenze setting
C01218
- Bit 3 SW limit positions for position follower on/off On
C01219
- Bit 3 SW limit positions for speed follower on/off On
C01230
- Bit 3 SW limit position for manual jogging on/off Off
efesotomasyon.com - Lenze