8400 HighLine | Parameter setting & configuration
I/O terminals
Configuring exception handling of the output terminals
244 L Firmware 05.00 - DMS 4.2 EN - 02/2010
6.4 Configuring exception handling of the output terminals
This function extension is only available from version 04.00.00!
Exception handling for the analog and digital output terminals in the event of an error can
be set via decoupling configuration and decoupling values.
Bit coded selection is carried out in C00441
for the analog output terminals, defining
the events that will trigger decoupling.
Bit coded selection is carried out in C00447
for the digital output terminals, defining
the events that will trigger decoupling.
Finally, the following parameters define the value/status that the output terminals are to
have when they are decoupled:
Related topics:
Configuring exception handling of the CAN PDOs
( 528)
Bit Event
Bit 0 SafeTorqueOff
Bit 1 ReadyToSwitchON
Bit 2 SwitchedON
Bit 3 Reserved
Bit 4 Trouble
Bit 5 Fault
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Fail CAN_Management
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Parameter Info Lenze setting
Value Unit
C00442/1 AOut1_U: Decoupling value 0.00 %
C00442/2
AOut2_U: Decoupling value 0.00 %
C00442/3
AOut1_I: Decoupling value 0.00 %
C00442/4
AOut2_I: Decoupling value 0.00 %
C00448
DigOut: Decoupling value Bit coded