Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 613
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00144
C00144
C00148
Parameter | Name:
C00144 | Switching freq. reduct. (temp.)
Data type: UNSIGNED_8
Index: 24431
d
= 5F6F
h
Activation of the automatic switching frequency reduction at too high temperature
Selection list (Lenze setting printed in bold) Info
0 Off Automatic switching frequency reduction deactivated
1On Automatic switching frequency reduction activated
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00148 | Config. group error
Data type: UNSIGNED_16
Index: 24427
d
= 5F6B
h
As of version 04.00.00
Selection of the device states for which the bCollectedFail group error output of the LS_DriveInterface
SB must be
set to TRUE.
Setting range (min. hex value | max. hex value) Lenze setting
0x0000 0xFFFF 0x0030 (decimal: 48)
Value is bit-coded: (; =bit set)
Bit 0 SafeTorqueOff
Bit 1 ReadyToSwitchON
Bit 2 SwitchedON
Bit 3 Reserved
Bit 4 ; Trouble
Bit 5 ; Fault
Bit 6 Warning
Bit 7 ImpIsActive
Bit 8 CInhIsActive
Bit 9 Fail CAN_Management
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
; Read access ; Write access CINH PLC STOP No transfer COM MOT