8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C01306
786 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
C01306
C01307
C01501
Parameter | Name:
C01306 | Profile data: S-ramp time
Data type: UNSIGNED_16
Index: 23269
d
= 5AE5
h
Selection of the S-ramp times for profiles 1 ... 15
• The maximum S-ramp time is the time in which the maximum acceleration or the maximum deceleration is
reached along a ramp (jerk limitation).
Profile entry
Setting range (min. value | unit | max. value)
0.000 s 10.000
Subcodes Lenze setting Info
C01306/1 0.000 s Profiles 1 ... 15: S-ramp time
C01306/...
C01306/15
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C01307 | Profile data: Sequence profile
Data type: UNSIGNED_8
Index: 23268
d
= 5AE4
h
Selection of the sequence profile numbers for profiles 1 ... 15
• For profile linkage
Profile entry
Setting range (min. value | unit | max. value)
015
Subcodes Lenze setting Info
C01307/1 0 Profiles 1 ... 15: Sequence profile
C01307/...
C01307/15
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C01501 | Resp. to communication error with MCI
Data type: UNSIGNED_8
Index: 23074
d
= 5A22
h
Configuration of monitoring functions for the communication module
Selection list
0 No Reaction
1Fault
2Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes Lenze setting Info
C01501/1 0: No Reaction Resp. to MCI error 1
• Response to a communication error of the attached
communication module.
C01501/2 0: No Reaction Resp. to MCI error 2
• Response to a missing or incompatible
communication module.
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1