8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00013
592 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
 
C00013
C00015
C00016
Parameter | Name:
C00013 | Decel. time - main setpoint
Data type: UNSIGNED_32
Index: 24562
d
 = 5FF2
h
FB L_NSet_1: Deceleration time of the ramp generator for the main speed setpoint
 • This ramp generator is basically used for all speed-controlled technology applications.
Setting range (min. value | unit | max. value) Lenze setting
0.000 s 999.999 2.000 s
; Read access ; Write access  CINH  PLC STOP  No transfer  COM  MOT Scaling factor: 1000
Parameter | Name:
C00015 | VFC: V/f base frequency
Data type: UNSIGNED_16
Index: 24560
d
 = 5FF0
h
V/f base frequency for VFCplus mode
 • The motor voltage increases linearly with the frequency until the base frequency is reached. From this value on, 
the motor voltage remains constant, the speed increases and the maximum torque decreases.
 • After the motor to be used has been selected from the motor catalogue, the suitable value can be entered 
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range (min. value | unit | max. value) Lenze setting
7.5 Hz 2600.0 50.0 Hz
; Read access ; Write access  CINH  PLC STOP  No transfer  COM ; MOT Scaling factor: 10
Parameter | Name:
C00016 | VFC: Vmin boost
Data type: UNSIGNED_16
Index: 24559
d
 = 5FEF
h
Boost of the V/f voltage characteristic within a small speed or frequency range for VFCplus mode
 • This may increase the starting torque.
 • After the motor to be used has been selected from the motor catalogue, the suitable value can be entered 
automatically. An automatic detection via the motor parameter identification is possible as well.
Motor control (MCTRL)
: Setting Vmin boost
Setting range (min. value | unit | max. value) Lenze setting
0.00 % 100.00 1.60 %
; Read access ; Write access  CINH  PLC STOP  No transfer  COM  MOT Scaling factor: 100