8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00089
604 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
C00089
C00090
C00091
C00092
C00093
Parameter | Name:
C00089 | Rated motor frequency
Data type: UNSIGNED_16
Index: 24486
d
= 5FA6
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor frequency for the field-oriented operating modes (SLVC and SC).
Setting range (min. value | unit | max. value) Lenze setting
1 Hz 1000 50 Hz
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 1
Parameter | Name:
C00090 | Rated motor voltage
Data type: UNSIGNED_16
Index: 24485
d
= 5FA5
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range (min. value | unit | max. value) Lenze setting
0 V 1000 400 V
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 1
Parameter | Name:
C00091 | Motor cosine phi
Data type: UNSIGNED_8
Index: 24484
d
= 5FA4
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range (min. value | unit | max. value) Lenze setting
0.40 1.00 0.85
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 100
Parameter | Name:
C00092 | Motor magnetising inductance
Data type: UNSIGNED_16
Index: 24483
d
= 5FA3
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range (min. value | unit | max. value) Lenze setting
0.0 mH 6500.0 81.0 mH
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 10
Parameter | Name:
C00093 | Power section ID
Data type: UNSIGNED_16
Index: 24482
d
= 5FA2
h
Display of the identification of the detected power section of the controller
Display range (min. value | unit | max. value)
0 65535
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00095 | Motor magnetising current
Data type: UNSIGNED_16
Index: 24480
d
= 5FA0
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range (min. value | unit | max. value) Lenze setting
0.00 A 320.00 8.50 A
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 100