Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 485
8400 HighLine | Parameter setting & configuration
Diagnostics & error management
Error messages of the operating system
SD10: Speed limit for feedback system 12 [xx.0123.00200]
SD11: Speed limit for feedback system 67 [xx.0123.00201]
SD3: Feedback system open circuit [xx.0123.00205]
An01: AIN1_I < 4 mA [xx.0125.00001]
An02: AIN2_I < 4 mA [xx.0125.00002]
Response (Lenze setting printed in bold) Setting: C00607 (; Adjustable response)
; None : Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Maximally permissible speed of the feedback system
connected to DI1/DI2 reached.
Reduce speed of the rotation shaft / feedback system.
n
encoder
<= (f
max
x 60) / encoder increments
(for f
max
= 10 kHz)
Response (Lenze setting printed in bold) Setting: C00607 (; Adjustable response)
; None : Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Maximally permissible speed of the feedback system
connected to DI6/DI7 reached.
Reduce speed of the rotation shaft / feedback system.
n
encoder
<= (f
max
x 60) / encoder increments
(for f
max
= 10 kHz)
Response (Lenze setting printed in bold) Setting: C00586 (; Adjustable response)
; None : Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
The device has detected open circuit in the feedback
system.
Check wiring of the feedback system and the
corresponding terminals.
Response (Lenze setting printed in bold) Setting: C00598/1 (; Adjustable response)
; None ; Fault ; Trouble : TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Open-circuit monitoring for analog input 1 has tripped.
• Only if the analog input has been configured as a
current loop of 4 ... 20 (C00034/1
=2).
• Check wiring of the analog X3/A1I input terminal for
open circuit.
• Check minimum current values of the signal sources.
Response (Lenze setting printed in bold) Setting: C00598/2 (; Adjustable response)
; None ; Fault ; Trouble : TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Open-circuit monitoring for analog input 2 has tripped.
• Only if the analog input has been configured as a
current loop of 4 ... 20 (C00034/2
=2).
• Check wiring of the analog X3/A2I input terminal for
open circuit.
• Check minimum current values of the signal sources.