8400 HighLine | Parameter setting & configuration
Diagnostics & error management
Error messages of the operating system
486 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
CE04: MCI communication error [xx.0127.00002]
CE0F: MCI control word [xx.0127.00015]
CE4: CAN bus off [xx.0131.00000]
CA06: CAN CRC error [xx.0131.00006]
CA07: CAN bus warning [xx.0131.00007]
Response (Lenze setting printed in bold) Setting: C01501/1 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
Communication error with extension module in slot 1. • Eliminate EMC interference.
• Switch off controller, correctly plug in the module,
switch on the controller again.
• Mains switching or restart of the controller,
respectively.
• Replace module/controller.
• If the problem occurs again, you needs to consult
Lenze.
Response (Lenze setting printed in bold) Setting: C00594/2 (; Adjustable response)
; None : Fault ; Trouble ; TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Bit 14 ("SetFail") of the wMciCtrl control word of the
LS_DriveInterface
system block has been set.
Trace back signal source on the bus (e.g. PROFIBUS) that
sets bit 14 ("SetFail").
Response (Lenze setting printed in bold) Setting: C00592/2 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
CAN on board: "Bus off" status
• Received too many faulty telegrams.
• Damaged cable (e.g. loose contact).
• Two nodes have the same ID.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign diiferent IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold) Setting: C00592/1 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
CAN on board: A faulty CAN telegram has been detected. • Check wiring and bus terminating resistor.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold) Setting: C00592/3 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
CAN on board: Incorrect transmission or reception of
more than 96 CAN telegrams.
• The current number of incorrectly transmitted CAN
telegrams is displayed in C00372/1
.
• The current number of incorrectly received CAN
telegrams is displayed in C00372/2
.
• The current CAN error status is displayed in C00345
.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign diiferent IDs to nodes.
• Eliminate electrical interference (e.g. EMC).