EasyManua.ls Logo

Lenze E84AVHC Series - 14.1.136.1 Function 0: Evaluate rising signal edges; 14.1.136.2 Function 1: Evaluate falling signal edges

Lenze E84AVHC Series
1118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware 05.00 - DMS 4.2 EN - 02/2010 L 1061
8400 HighLine | Parameter setting & configuration
Function library
Function blocks | L_Transient_1
14.1.136.1 Function 0: Evaluate rising signal edges
[14-44] Switching performance for function selection "0: High edge"
Functional sequence
1. A FALSE-TRUE edge at the bIn input sets the bOut output to TRUE.
2. After the parameterised pulse duration has elapsed, the bOut output is reset to FALSE
unless another FALSE/TRUE edge has been set at the bIn input.
If an additional FALSE-TRUE edge occurs at the bIn input, the pulse duration starts
again from the beginning, i.e. the bOut output can be retriggered.
14.1.136.2 Function 1: Evaluate falling signal edges
[14-45] Switching performance for function selection "1: Low edge"
Functional sequence
1. A TRUE-FALSE edge at the bIn inputs sets the bOut output to TRUE.
2. After the parameterised pulse duration has elapsed, the bOut output is reset to FALSE
unless another TRUE/FALSE edge has been set at the bIn input.
If an additional TRUE-FALSE edge occurs at the bIn input, the pulse duration starts
again from the beginning, i.e. the bOut output can be retriggered.
n Pulse duration
TRUE
FALSE
bOut
t
TRUE
FALSE
bIn
t

n Pulse duration
TRUE
FALSE
bOut
t
TRUE
FALSE
bIn
t
