Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 79
8400 HighLine | Parameter setting & configuration
Device control (DCTRL)
Device states
4.2.3 MotorIdent
The controller has been provided with a function for automatic identification of the motor
parameters. If the motor parameter identification is active, the controller is in the
"MotorIdent" device state.
The "MotorIdent" device state can only be reached by the "SwitchedON
" device state
and jumps back to that state after the activity has been completed.
The following illustration shows the conditions under which the state change will be
enabled or stopped:
[4-2] Conditions for the state change of the motor identification
While the motor parameters are being detected,
the application remains active,
all system interfaces (IO, bus systems, etc.) remain active,
error monitoring remains active,
the inverter is controlled independently of the setpoint sources.
Tip!
Detailed information on motor parameter identification can be found in the
"Automatic motor data identification
" subchapter on motor control. ( 102)
LED DRIVE READY LED DRIVE ERROR Display in C00137 Display in status word 1 (C00150)
Bit 11 Bit 10 Bit 9 Bit 8
Off MotorIdent 0 0 1 0
Stop!
During motor parameter identification, the controller does not respond to
setpoint changes or control processes, (e.g. speed setpoints, quick stop, torque
limitations).
SwitchedOn
4
C00002/23 = 1
CINH = 1
MotorIdent
2
&