Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 589
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00007
C00007
C00008
Parameter | Name:
C00007 | Select control mode
Data type: UNSIGNED_16
Index: 24568
d
= 5FF8
h
With this parameter the control mode for the technology application selected under C00005 is defined, i.e. how the
inputs and outputs of the technology application are connected to the I/Os of the controller.
• How the inputs and outputs are connected in the individual control modes is described in the corresponding
technology application.
TA "Actuating drive speed"
TA "Table positioning"
TA "Switch-off positioning"
Selection list (Lenze setting printed in bold) Info
0 Wiring has changed This is displayed when the FB interconnection has been
changed in the I/O level via the FB Editor.
10 Terminals 0 The technology application is controlled via the digital
and analog input terminals of the controller.
12 Terminals 2 The technology application is controlled via the digital
and analog input terminals of the controller.
14 Terminals 11 The technology application is controlled via the digital
and analog input terminals of the controller.
16 Terminal 16 The technology application is controlled via the digital
and analog input terminals of the controller.
20 Keypad The technology application is controlled via the keypad.
21 PC The technology application is controlled via the "Free
parameters" of the controller (PC control).
30 CAN The technology application is controlled by means of
CAN-PDOs via the system bus "CAN on board".
System bus "CAN on board"
40 MCI The technology application is controlled by means of
MCI-PDOs via the MCI-interface of an attached
communication module (e.g. PROFIBUS).
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00008 | Original application|Control source
Data type: UNSIGNED_16
Index: 24567
d
= 5FF7
h
Display of the originally selected technology application and the originally selected control mode.
• This parameter shows the selection that was set with C00005
and C00007 before a change in the I/O level or the
application level was carried out.
• For purposes of diagnostics this display can be used to determine whether there is a standard signal
interconnection within the controller, or whether a change was carried out by the user.
Selection list (read only) Info
0 Free|Free Application: Interconnection changed
I/O level: Interconnection changed
10 Free|Terminal0 Application: Interconnection changed
I/O level: "Terminals 0" control mode
12 Free|Terminal2 Application: Interconnection changed
I/O level: "Terminal 2" control mode
14 Free|Terminal11 Application: Interconnection changed
I/O level: "Terminal 11" control mode
16 Free|Terminal 16 Application: Interconnection changed
I/O level: "Terminal 16" control mode
20 Free|Keypad Application: Interconnection changed
I/O level: "Keypad" control mode
21 Free|PC Application: Interconnection changed
I/O level: "PC" control mode
30 Free|CAN Application: Interconnection changed
I/O level: "CAN" control mode
efesotomasyon.com - Lenze