Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 647
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00364
C00364
C00366
C00367
C00368
Parameter | Name:
C00364 | CAN MessageError
Data type: UNSIGNED_8
Index: 24211
d
= 5E93
h
System bus "CAN on board"
Selection list (read only)
0 No Error
1 StuffError
2 FormError
3 AckError
4 Bit1Error
5 Bit0Error
6 CRCError
7 Reserved
; Read access Write access CINH PLC STOP ; No transfer ; COM MOT Scaling factor: 1
Parameter | Name:
C00366 | CAN1_OUT transmit at sync
Data type: UNSIGNED_8
Index: 24209
d
= 5E91
h
In the Lenze setting "Yes", the device transmits CAN1_OUT after receipt of the sync telegram if the transmission
mode for CAN1_OUT is set to 1 ... 240 in C00322/1
.
System bus "CAN on board"
Selection list (Lenze setting printed in bold)
0No
1Yes
; Read access ; Write access CINH PLC STOP No transfer ; COM MOT Scaling factor: 1
Parameter | Name:
C00367 | CAN Sync-Rx identifier
Data type: UNSIGNED_16
Index: 24208
d
= 5E90
h
Identifier by means of which the sync slave is to receive sync telegrams.
• Mapping of the CANopen object I-1005
(see DS301 V4.02).
System bus "CAN on board": Sync telegram
Setting range (min. value | unit | max. value) Lenze setting
1 255 128
; Read access ; Write access CINH PLC STOP No transfer ; COM MOT Scaling factor: 1
Parameter | Name:
C00368 | CAN Sync-Tx identifier
Data type: UNSIGNED_16
Index: 24207
d
= 5E8F
h
Identifier by means of which the sync master is to transmit sync telegrams.
• Mapping of the CANopen object I-1005
(see DS301 V4.02).
System bus "CAN on board": Sync telegram
Setting range (min. value | unit | max. value) Lenze setting
1 255 128
; Read access ; Write access CINH PLC STOP No transfer ; COM MOT Scaling factor: 1