8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00964
754 L Firmware 05.00 - DMS 4.2 EN - 02/2010
C00964
C00966
C00967
Parameter | Name:
C00964 | L_Curve_1: Table of Y values
Data type: INTEGER_16
Index: 23611
d
= 5C3B
h
As of version 04.00.00
L_Curve_1
: Y values for characteristic function
Setting range (min. value | unit | max. value)
-32767 32767
Subcodes Lenze setting Info
C00964/1 0 Y values 1 ... 32 for characteristic function
C00964/...
C00964/32
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00966 | VFC: Time const. - slip compens.
Data type: UNSIGNED_16
Index: 23609
d
= 5C39
h
Filter time constant of the slip compensation for VFCplus mode
The slip compensation time constant can be used to select the dynamic performance of the slip compensation
for non-feedback V/f characteristic control.
The lower the selected time constant, the higher the dynamic performance of the slip compensation.
Setting range (min. value | unit | max. value) Lenze setting
1 ms 6000 100 ms
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00967 | VFC: Frequency at curve interpolation point n
Data type: INTEGER_16
Index: 23608
d
= 5C38
h
As of version 04.00.00
Selection of the curve interpolation points (frequency values) for the VFCplus operating mode with user-definable
V/f characteristic (C00006
="10")
Setting range (min. value | unit | max. value)
-2600.0 Hz 2600.0
Subcodes Lenze setting Info
C00967/1 -50.0 Hz VFC: Frequency at curve interpolation point 1
C00967/2 -40.0 Hz VFC: Frequency at curve interpolation point 2
C00967/3 -30.0 Hz VFC: Frequency at curve interpolation point 3
C00967/4 -20.0 Hz VFC: Frequency at curve interpolation point 4
C00967/5 -10.0 Hz VFC: Frequency at curve interpolation point 5
C00967/6 0.0 Hz VFC: Frequency at curve interpolation point 6
C00967/7 10.0 Hz VFC: Frequency at curve interpolation point 7
C00967/8 20.0 Hz VFC: Frequency at curve interpolation point 8
C00967/9 30.0 Hz VFC: Frequency at curve interpolation point 9
C00967/10 40.0 Hz VFC: Frequency at curve interpolation point 10
C00967/11 50.0 Hz VFC: Frequency at curve interpolation point 11
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10