8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00671
688 L Firmware 05.00 - DMS 4.2 EN - 02/2010
C00671
C00672
C00673
C00674
C00677
Parameter | Name:
C00671 | L_OffsetGainP_2: Gain
Data type: INTEGER_32
Index: 23904
d
= 5D60
h
FB L_OffsetGainP_2: Gain as multiplier of input signal + offset
Setting range (min. value | unit | max. value) Lenze setting
-100.0000 100.0000 1.0000
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10000
Parameter | Name:
C00672 | L_OffsetGainP_3: Gain
Data type: INTEGER_32
Index: 23903
d
= 5D5F
h
FB L_OffsetGainP_3: Gain as multiplier of input signal + offset
Setting range (min. value | unit | max. value) Lenze setting
-100.0000 100.0000 1.0000
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10000
Parameter | Name:
C00673 | L_OffsetGainPhiP 1-2: Offset
Data type: INTEGER_32
Index: 23902
d
= 5D5E
h
Angular offset (is added to the angular input signal)
Setting range (min. value | unit | max. value)
-2147483647 Incr. 2147483647
Subcodes Lenze setting Info
C00673/1 0 incr. L_OffsetGainPhiP_1
: Offset
C00673/2 0 incr. L_OffsetGainPhiP_2
: Offset
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00674 | L_OffsetGainPhiP 1-2: Gain
Data type: INTEGER_32
Index: 23901
d
= 5D5D
h
Angular gain as multiplier of the input signal + angular offset
Setting range (min. value | unit | max. value)
-2147483647 2147483647
Subcodes Lenze setting Info
C00674/1 0 L_OffsetGainPhiP_1: Gain
C00674/2 0 L_OffsetGainPhiP_2
: Gain
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00677 | L_GainOffsetP 1-3: Parameter
Data type: INTEGER_16
Index: 23898
d
= 5D5A
h
Gain and offset
Setting range (min. value | unit | max. value)
-199.99 % 199.99
Subcodes Lenze setting Info
C00677/1 100.00 % L_GainOffsetP_1
: Gain
C00677/2 0.00 % L_GainOffsetP_1: Offset
C00677/3 100.00 % L_GainOffsetP_2
: Gain
C00677/4 0.00 % L_GainOffsetP_2
: Offset
C00677/5 100.00 % L_GainOffsetP_3
: Gain
C00677/6 0.00 % L_GainOffsetP_3
: Offset
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100