8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
Braking operation/braking energy management
192 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
5.10.1 Setting the voltage source for braking operation
The voltage threshold for braking is set by means of the mains voltage (C00173
) and the
lowered brake chopper threshold (C00174
).
This "brake chopper threshold" is preset as follows so that it is higher than the specified
mains voltage (C00173
):
This brake chopper threshold can be reduced by 0 ... 150 V by means of C00174
.
Example:
A 400 V device has a maximum mains voltage of 420 V AC.
– Maximum stationary DC-bus voltage: 420 V AC * 1.414 = 594 V DC
– C00173
has been set with the selection "0" for 400 V AC mains.
This means that C00174
can be set to a maximum of 131 V DC (725 V DC - 594 V DC).
Mains voltage Brake chopper threshold
C00173 1-phase 3-phase 1-phase 3-phase
0 1ph 230V 3ph 400V 380V DC 725V DC
1 1ph 230V 3ph 440V 380V DC 35V DC
2 1ph 230V 3ph 480V 380V DC 775V DC
3 1ph 230V 3ph 500V 380V DC 790V DC
4 1ph 115V 3ph 400V 205V DC 725V DC
Stop!
The brake chopper threshold resulting from C00173 and C00174 must not
exceed the stabilised DC-bus voltage!