8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00020
594 L Firmware 05.00 - DMS 4.2 EN - 02/2010
C00020
C00021
C00022
C00023
Parameter | Name:
C00020 | AIN2: Characteristic
Data type: INTEGER_16
Index: 24555
d
= 5FEB
h
As of version 04.00.00
Analog terminals
: Signal adaptation via characteristic
Setting range (min. value | unit | max. value)
0.00 % 199.99
Subcodes Lenze setting Info
C00020/1 0.00 % AIN2: (+y0) = min
C00020/2 0.00 % AIN2: (+x0) = Dead band
C00020/3 0.00 % AIN2: (-y0) = (-min)
C00020/4 0.00 % AIN2: (-x0) = (-Dead band)
C00020/5 100.00 % AIN2: (+ymax)
C00020/6 100.00 % AIN2: (+xmax)
C00020/7 100.00 % AIN2: (-ymax)
C00020/8 100.00 % AIN2: (-xmax)
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00021 | Slip compensation
Data type: INTEGER_16
Index: 24554
d
= 5FEA
h
Slip compensation for VFCplus and SLVC modes
An increase of the slip compensation causes a greater frequency and voltage increase when the machine is
loaded.
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Motor control (MCTRL)
: Optimising the operational performance by slip compensation
Setting range (min. value | unit | max. value) Lenze setting
-100.00 % 100.00 2.67 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00022 | Imax in motor mode
Data type: UNSIGNED_16
Index: 24553
d
= 5FE9
h
Maximum current in motor mode for all operating modes
Setting range (min. value | unit | max. value) Lenze setting
0.00 A 655.35 47.00 A
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00023 | Imax in generator mode
Data type: INTEGER_16
Index: 24552
d
= 5FE8
h
Maximum current in generator mode for all operating modes
•100% Imax in motor mode (C00022
)
Setting range (min. value | unit | max. value) Lenze setting
0.00 % 100.00 100.00 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100