Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 69
8400 HighLine | Parameter setting & configuration
Device control (DCTRL)
Controller commands
4.1.1 Load Lenze setting
The C00002/1
= "1: On / start" controller command resets the parameters to the Lenze
setting which are saved in the controller Firmware.
Can only be executed if the controller is inhibited; otherwise, the feedback C00002/
1 = "6: No access - controller inhibit" will be returned.
All parameter changes which have been carried out after the last time the parameter
set was saved will be lost!
This controller command has an effect on the settings of the parameters of the
operating system, application and module.
How to load the Lenze setting:
1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/
Inhibit controller" controller command (C00002/16
= "0: Off / ready").
2. Execute the "Load Lenze setting" controller command:
C00002/1
= "1: On / start"
The loading process may take a couple of seconds. After the controller command
has been called in C00002/1
, dynamic status information ("Work in progress 20%"
"Work in progress 40%" "Work in progress 60%", etc.) is returned.
efesotomasyon.com - Lenze