Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 633
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00253
C00253
C00254
C00265
C00270
C00271
Parameter | Name:
C00253 | L_DT1_1: Sensitivity
Data type: UNSIGNED_8
Index: 24322
d
= 5F02
h
FB L_DT1_1: Selection of sensitivity
• Depending on the selection, the number of indicated higher-order bits is evaluated.
Note:
The most significant bit determines the sign of the value, the remaining bits determine the numerical value.
Selection list (Lenze setting printed in bold) Info
1 15 Bit Bit 0 ... bit 14 are evaluated
2 14 Bit Bit 0 ... bit 13 are evaluated
3 13 Bit Bit 0 ... bit 12 are evaluated
4 12 Bit Bit 0 ... bit 11 are evaluated
5 11 bits Bit 0 ... bit 10 are evaluated
6 10 bits Bit 0 ... bit 9 are evaluated
7 9 bits Bit 0 ... bit 8 are evaluated
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00254 | Kp position controller
Data type: UNSIGNED_16
Index: 24321
d
= 5F01
h
Gain for following error compensation
Setting range (min. value | unit | max. value) Lenze setting
0.00 1/s 500.00 5.00 1/s
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00265 | SLVC: Tn torque controller
Data type: UNSIGNED_8
Index: 24310
d
= 5EF6
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00270 | SC: Freq. current setpoint filter
Data type: UNSIGNED_16
Index: 24305
d
= 5EF1
h
Frequency to be inhibited by the current setpoint filter for SC (servo control) mode.
Setting range (min. value | unit | max. value) Lenze setting
40.0 Hz 1000.0 200.0 Hz
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 10
Parameter | Name:
C00271 | SC: Width - current setp. filter
Data type: UNSIGNED_16
Index: 24304
d
= 5EF0
h
Frequency width of the current setpoint filter for SC (servo control) mode
• Width around the frequency to be inhibited (C00270
).
Setting range (min. value | unit | max. value) Lenze setting
0.0 Hz 500.0 0.0 Hz
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 10