Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 191
8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
Braking operation/braking energy management
 
 Tip!
In C00175
, a ramp function generator stop (FB L_NSet_1) can be set for instances
when the brake resistor is controlled. This prevents overvoltage deactivation in the
case of short deceleration times.
Selecting the response to an increase of the DC-bus voltage
 ( 193) 
Short overview of the relevant parameters:
 To install the regenerative module, follow the instructions in the hardware 
manual.
All the necessary instructions for the drive controller are stored in electronic 
form on the data carrier supplied with the 8400 drive controller.
Parameter Info Lenze setting
Value Unit
C00129 Brake resistance value 39.0 Ohm
C00130
Rated brake resistor power 100 w
C00131
Thermal capacity of brake resistor 10.0 kWs
C00133 Brake resistor utilisation - %
C00173
Mains voltage 3ph 400 V / 1ph 230 V
C00174
Reduced brake chopper threshold 0 V
C00175
Response for brake resistor control Brake resistor
C00572
Brake resistor overload threshold 100 %
C00574
Response to brake resistor overtemperature No response
C00987
Inverter motor brake: nAdd 80 rpm
C00988
Inverter motor brake: PT1 filter time 0.0 ms
Highlighted in grey = display parameter