Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 253
8400 HighLine | Parameter setting & configuration
I/O terminals
Electrical data
 
Digital output terminals
   
Terminal Use Electrical data
X4/DO1
...
X4/DO3
Digital output 1 ... 3 LOW level: 0 ... +5 V
HIGH level: +15 ... +30 V
Output current: max. 50 mA per output (external resistance 
>480Ω at 24 V)
Processing cycle: 1 ms
X4/24E External 24 V voltage supply for, among other things, the digital outputs
X4/GIO Reference potential (digital ground)
X101/COM Relay output, 
common contact
Potential-free two-way switch
AC 250  V / 3 A
24 V DC / 2 A ... 240 V / 0.16 A
X101/NC Relay output, NC 
contact
X101/NO Relay output, NO 
contact
X107/BD1 Brake, positive 
connection
X107/BD2 Brake, negative 
connection
X107/GB Brake, reference 
potential
X4
DO1
24O
DO2
DO3
GO
X101
NC
COM
NO
X107
GB
24B
BD1
BD2
efesotomasyon.com - Lenze