8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
V/f characteristic control (VFCplus)
118 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
 
 Note!
4-pole asynchronous motors which are designed for a rated frequency of f = 50 
Hz in star connection can be operated in delta connection when being constantly 
excited up to f = 87 Hz.
 • Advantages:
– Higher speed-setting range
– 73% higher power output in case of standard motors
 • Motor current and motor power increase by the factor .
 • The field weakening range starts above 87 Hz.
 • Generally, this process can also be used with motors which have different 
numbers of pole pairs. In case of 2-pole asynchronous motors, the mechanical 
limit speed must be maintained.
3