Firmware 05.00 - DMS 4.2 EN - 02/2010 L 113
8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
V/f characteristic control (VFCplus)
Short overview of the relevant parameters:
Control structure
The illustration below shows the control structure in a simplified way. A complete
representation can be found in the "Signal flow
" subchapter. ( 126)
[5-3] Control structure of the V/f characteristic control (VFCplus)
Parameter Info
C00006
Selection of the operating mode for V/f characteristic control without
feedback with
value "6" for linear characteristic or
Value "8" for quadratic characteristic or
Value "10" for freely definable characteristic (as of version 04.00.00)
C00011
Reference speed
C00015
Base frequency
C00016
V
min
boost
C00018
Switching frequency
C00021
Slip compensation
C00022
Current limit (in motor mode)
C00023
Current limit (in generator mode)
C00073/1
I
max
current controller gain
C00074/1
I
max
current controller reset time
C00080
Override point of field weakening function
C00909/1 /2
Maximum positive / negative speed
C00910/1 /2
Maximum positive / negative output frequency
f :
C00910/1 /2
max
n :
C00909/1 /2
max
nStatorCurrentIS_a
C00054
nEffSpeedSetValue_a
C00050
I :C00022
I :C00023
max Mot
max Gen
V :C00073/1
p
T :C00074/1
N
nSpeedSetValue_a
C00830/22
Hz
%
nMotorFreqAct_a
C00058
f
Mod
Slipcomp
C00021
Slip compensation
I controller
max
ModulatorCharacteristic
selection
Motor slip model
f : C00015
V : C00016
base
min
V
set
efesotomasyon.com - Lenze