8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
Parameterisable additional functions
172 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
 
Short overview of the relevant parameters:
 How to parameterise the flying restart function:
1. Activate the flying restart circuit by selecting "1: On" in C00990
. 
 • Every time the controller is enabled, a synchronisation to the rotating or 
standing drive is carried out. 
When the Lenze setting is used, most applications do not require additional 
controller settings.
If additional settings are necessary, proceed as follows:
2. Define the process and hence the speed range/rotational frequency range in 
C00991
 which is to be examined by the flying restart circuit:
 • positive speed range (n
≥ 0min
-1
)
 • negative speed range (n
≤ 0min
-1
)
 • total speed range
3. Define the starting frequency.
The starting frequency which defines the starting point of the flying restart 
function is 10 or -10 Hz for processes 0 ... 3 and has been pre-optimised for 
standard motors.
If process 4 is selected in C00991
, an arbitrary starting frequency can be defined via 
C00992
. This is especially recommended for motors with higher rated frequencies.
 • We recommend to define a starting frequency of approximately 20 % of the 
rated motor frequency to enable a safe and fast connection to standing drive 
systems. 
 • For systems with a known search speed (e.g. torque-controlled drive systems 
which are to synchronise to a defined speed) the starting value can be adapted 
to reduce the flying restart time.
4. Set the flying restart current in C00994
.
We recommend setting a flying restart current of 10 % ... 25 % of the rated motor 
Parameter Info Lenze setting
Value Unit
C00990 Flying restart fct: Activation Off
C00991
Flying restart fct: Traverse -n...+n | Start: +10 Hz
C00992
Flying restart fct: Starting frequency 5 Hz
C00994
Flying restart fct: Current 25.00 %