Firmware 05.00 - DMS 4.2 EN - 02/2010 L 177
8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
Parameterisable additional functions
Explanation of the automatic DC-injection braking function by means of two examples
[5-24] Example 1: Signal characteristic for automatic DC-injection braking of a drive without speed feedback
Speed setpoint
Actual speed value of the motor
Output current of the controller
Pulse inhibit
DC-injection braking is active
c The motor rotates at a
specified speed. The current
adjusts itself to the load, see .
d The DC braking current set in
C00036
is injected.
e After the hold time (C00106)
has expired, a pulse inhibit is set.
0
1
2
3
4
C0107
C00036
C00019
efesotomasyon.com - Lenze