Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 375
8400 HighLine | Parameter setting & configuration
Basic drive functions (MCK)
MCKInterface
 
Control of the Motion Control Kernel
Control of the basic drive functions implemented in the Motion Control Kernel is carried
out by means of
 direct
 specification of the control words, for example via a master control unit also 
connected to the fieldbus. 
– For this purpose, the control word inputs can be directly connected to the field bus 
interface LP_MciIn respectively LP_CanIn.
– See the "MCK control word
" chapter for a detailed description of the individual 
control bits.
 the specification of individual process signals at the L_MckCtrlInterface
 FB which are 
then ORed with the control word.
Plausibility check
The process signals applied to the L_MckCtrlInterface
 FB are logically linked by means of an
OR logic operation to the specified control word via the two control word inputs
wInMckPosCtrl_1 and wInMckPosCtrl_2  and, after a plausibility check, are output via the
two control word outputs wOutMckPosCtrl_1 and wOutMckPosCtrl_2 .
 The profile number, the operating mode, and the positioning mode are checked for 
plausibility.
 If implausibility is detected, only control bit information is output and the bFail output 
is set to TRUE.
 The result of the plausibility check is provided as the wFailState output word and 
displayed in C01299
.
The control words that are output, namely wOutMckPosCtrl_1 and wOutMckPosCtrl_2,
constitute the input information for the LS_MotionControlKernel
 system block.
Status information of the Motion Control Kernel
Output by the LS_MotionControlKernel
, the status words wMotionState1 and
wMotionState2 also constitute input information for the
downstream L_MckStateInterface
 FB, which provides this information to the application
in the form of process signals.