8400 HighLine | Parameter setting & configuration
Diagnostics & error management
Error messages of the operating system
476 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
 
xx.0145.00022 dF22: CU watchdog Fault - 0x6100
xx.0145.00025
dF25: CU RCOM error Fault - 0x6100
xx.0145.00035
dF35: AutoTrip reset Fault C00189 0xF000
xx.0145.00050
dF50: Retain error Fault - 0x6100
xx.0400.00009
dH09: EEPROM power section Fault - 0x5530
xx.0400.00016
dH10: Fan failure Warning C00566 0x5000
xx.0400.00105
dH69: Adjustment fault Fault - 0x5530
xx.0123.00099
FC1: Field controller limitation No response C00570/4 0xF000
xx.0123.00094
FCH1: Switching frequency reduction No response C00590 0x2000
xx.0123.00095
FCH2: Maximum speed for Fchop No response C00588 0xF000
xx.0123.00057
ID1: Motor data identification error WarningLocked - 0xF000
xx.0123.00058
ID3: CINH motor data identification WarningLocked - 0xF000
xx.0123.00059
ID4: Resistance identification error Warning - 0xF000
xx.0123.00145
LP1: Motor phase failure No response C00597 0x3000
xx.0123.00015
LU: DC bus undervoltage Trouble C00600/1 0x3100
xx.0140.00013
MCI1: Module missing/incompatible No response C01501/2 0x7000
xx.0123.00016
OC1: Power section - short circuit Fault - 0x2000
xx.0123.00017
OC2: Power section - earth fault Fault - 0x2000
xx.0119.00050
OC5: Ixt overload Warning C00604 0x2000
xx.0123.00105
OC6: I2xt overload - motor Warning C00606 0x2000
xx.0123.00030
OC10: Maximum current reached Fault - 0x2000
xx.0123.00071
OC11: Clamp operation active Warning - 0xF000
xx.0123.00065
OC12: I2xt brake resistance overload Fault - 0xF000
xx.0123.00090
OC13: Maximum current for Fch exceeded Fault - 0xF000
xx.0123.00096
OC14: Direct-axis current controller limitation No response C00570/1 0xF000
xx.0123.00097
OC15: Cross current controller limitation No response C00570/2 0xF000
xx.0123.00098
OC16: Torque controller limitation No response C00570/3 0xF000
xx.0123.00031
OC17: Clamp sets pulse inhibit No response C00569/1 0xF000
xx.0119.00001
OH1: Heatsink overtemperature Fault - 0x4000
xx.0119.00015
OH3: Motor temperature (X106) triggered Fault C00585 0x4000
xx.0119.00000
OH4: Heatsink temp. > shutdown temp. -5°C No response C00582 0x4000
xx.0123.00032
OS1: Maximum speed limit reached No response C00579 0x8400
xx.0123.00001
OT1: Maximum torque reached No response C00608 0x8300
xx.0123.00093
OT2: Speed controller output limited No response C00567 0xF000
xx.0123.00014
OU: DC bus overvoltage Trouble - 0x3100
xx.0144.00001
PS01: No memory module Warning - 0x6300
xx.0144.00002
PS02: Par. set invalid Fault - 0x6300
xx.0144.00003
PS03: Par. set device invalid Fault - 0x6300
xx.0144.00004
PS04: Par. set Mci invalid Fault - 0x6300
xx.0144.00007
PS07: Par. mem. module invalid Fault - 0x6300
xx.0144.00008
PS08: Par. device invalid Fault - 0x6300
xx.0144.00009
PS09: Par. format invalid Fault - 0x6300
xx.0123.00205
SD3: Feedback system open circuit Fault C00586 0x7300
xx.0123.00200
SD10: Speed limit for feedback system 12 Fault C00607 0x7300
xx.0123.00201
SD11: Speed limit for feedback system 67 Fault C00607 0x7300
xx.0111.00002
Su02: Mains voltage switched off Warning C00565 0x3000
xx.0111.00003
Su03: Too frequent mains switching Fault - 0x3000
xx.0111.00004
Su04: CU Insufficiently Supplied Fault - 0x3000
xx.0980.00000
US01: User error 1 No response C00581/1 0x6200
xx.0981.00000
US02: User error 2 No response C00581/2 0x6200
xx.0982.00000
US03: User error 3 No response C00581/3 0x6200
Error number Error message Response 
(Lenze setting)
can be set in CAN Emergency 
Error Code