Firmware 05.00 - DMS 4.2 EN - 02/2010 L 541
8400 HighLine | Parameter setting & configuration
System bus "CAN on board"
Parameter data transfer
Telegram 3 to the drive: Request of the 2nd data block
Response telegram 3 from the drive: Transmission of the 2nd data block including end
identifier
Identifier User data
1st byte 2nd byte 3rd byte 4th byte 5th byte 6th byte 7th byte 8th byte
Command Data 1 Data 2 Data 3 Data 4 Data 5 Data 6 Data 7
0x060C 0x70 0x00 0x00 0x00 0x00 0x00 0x00 0x00
Explanations on telegram 3 to the drive
Command = 0x70 = "Read segment request" (request: read data block)
Bit 4 = 1 (toggle bit)
Identifier User data
1st byte 2nd byte 3rd byte 4th byte 5th byte 6th byte 7th byte 8th byte
Command Data 1 Data 2 Data 3 Data 4 Data 5 Data 6 Data 7
0x058C 0x17 0x30 0x2E 0x30 0x30 0x00 0x00 0x00
0
asc
.
asc
0
asc
0
asc
---
Explanations on telegram 3 from the drive
Command = 0x17 = 00010111
bin
:
Bit 0 = 1 (end of transmission)
Bit 1 ... bit 3 = 011
bin
(3 bytes do not contain any data)
Bit 4 = 1 (toggle bit)
Influence of the final bit and the residual data length on the transmission command
The end of transmission is signalled via the set final bit 0.
Bits 1 ... 3 reveal the number of bytes that do not contain any data anymore.
* Toggle bit
Data 1 ... 7 = "0.00" (ASCII representation)
The result of the data block transmission is: "01.00.00.00"