Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 555
8400 HighLine | Parameter setting & configuration
System bus "CAN on board"
Implemented CANopen objects
 
I-1016
Monitoring time for the nodes to be monitored via heartbeat. Heartbeat protocol ( 543) 
 The parameterised time is rounded down to an integer multiple of 5 ms and must have 
a greater value than the heartbeat producer time of the node to be monitored.
[10-4] Data telegram assignment
Index:
I-1016
Name:
Consumer heartbeat time
Subindex Default setting Setting range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 1 (for BaseLine)
7 (for StateLine)
15 (for HighLine)
- (read access only) ro U16
1 ... n: Consumer heartbeat time 0 0 65535 rw U16
Subindex Meaning Lenze code
0 Number of nodes to be monitored
1 ... n Node ID and heartbeat time of the node to be monitored Node ID:
C00385/x
Heartbeat time:
C00386/x
8th byte 7th byte 6th byte 5th byte
Data 4 Data 3 Data 2 Data 1
Bit 31 ... bit 24 Bit 23 ... Bit 16 Bit 15 ... Bit 0
0
Reserved
Node ID Heartbeat time