8400 HighLine | Parameter setting & configuration
System bus "CAN on board"
Implemented CANopen objects
568 L Firmware 05.00 - DMS 4.2 EN - 02/2010
I-1802
Communication parameter for sending process data via TPDO3
For data telegram assignment and description of subindices, see object I-1800
.
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1802
Name:
TPDO3 communication parameter
Subindex Default setting Setting range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 5 - (read access only) ro U8
1: COB-ID used by TPDO 0x380 + node ID 0 4294967295 rw U32
2: Transmission type 254 0 255 rw U8
3: Inhibit time 0 ms 0 0.1 ms 65535 rw U16
4: Reserved - - (reserved, read or write access leads to error message
0x06090011)
rw U8
5: Event timer 0 ms 0 ms 65535 rw U16
Subindex Meaning Code
0 "5" is permanently set.
Max. 5 subindicesare supported.
-
1 TPDO3 identifier
According to the "Predefined Connection Set", the
basic setting is: Identifier = 0x380 + node ID
C00354/6
2 TPDO transmission type according to DS301 V4.02
Transmission type
( 525)
C00322/3
3 Minimum time between sending two identical TPDOs
(see DS301 V4.02).
-
5 Cycle time for PDO transmission with transmission type
"254".
C00356/3
C00369