Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 39
8400 HighLine | Parameter setting & configuration
Commissioning
Quick commissioning
 
4. Set keypad control
5. Enable controller:
Set terminal X5/RFR to HIGH potential (reference: X5/24I).
6. Use the keypad to change the motor velocity or 
the motor speed by selecting different fixed setpoints:
 • Scroll to the bottom from the 
"User menu" with the button to 
the "Quick commissioning" menu
 • Click on right-hand button
 • Select the "Keypad" menu
 • Click on right-hand button
 • Code C00002/1:
–Parameterise "Edit" using the 
left function key
–Select value "1" ---> On/Start 
and confirm with "OK" function 
key on right
During loading the Lenze setting, the 
display goes off for a short time.
 • With the Lenze setting, the 
"Actuating drive speed" 
technology application is 
implemented.
 • When the display reappears, the 
main menu is shown.
–The main menu can be set in a 
user-defined manner via the 
codes C00465 ... C00469.
 • Use the left function key to go to 
the USER menu
 • Continue as described in 
commissioning point 3:
–"Quick commissioning" menu
–Keypad
–Load Lenze setting
 • With the "Bottom" navigation 
key, code C00007 for selecting the 
control mode is reached:
–Select code C00007 and 
parameterise with "Edit"
–Select value "20" ---> "Keypad" 
and confirm with "OK".
Keypad Code Subcode Motor speed
C00728 3 Counter-clockwise rotation:
-199.99 % ..... 0 (from C00011)
Clockwise rotation:
0 ... +199.99 % (from C00011) 
C00051 - Display of actual speed value
SAVE
Par1 8400 HighLineC
User - Menu
Logbook
Go to param
Quick commissioning
SAVE
Par1 Quick commissioning
Terminals
Keypad
EDIT
Load Lenze setting
C00002/1
MCTRL: Act. speed val.
C00051
0 rpm
EDIT
Select CtrlMode
C00007
Quick commissioning
SAVE
Par1 Quick commissioning
Terminals
Keypad
SAVE
Par1 8400 HighLineC
User - Menu
Logbook
Go to param
Quick commissioning
EDIT
Load Lenze setting
C00002/1
EDIT
< ... >
C00728
C00051
SAVE
Par1 Quick commissioning
Terminals
Keypad