8400 HighLine | Parameter setting & configuration
Commissioning
Quick commissioning
40 L Firmware 05.00 - DMS 4.2 EN - 02/2010
Please observe
the actual speed value: C00051
the LEDs on the front LED’s.LED status displays of the device state
( 454)
7. Save parameter settings with in the memory module.
Available codes in the "Quick commissioning" menu
If you select suitable and reasonable values for the parameters in this menu, you can
ensure an error-free operation of the controller.
Analog and digital control information (e.g. speed setpoint, CW rotation / CCW rotation)
are selected depending on the setting of C00007
(e.g. selection through the digital inputs).
Parameter Display in the keypad Info
C00002/1
Load Lenze setting Load Lenze setting
C00007
Select CtrlMode Selecting the operating mode
C00728/3
nMainSetValue_a Main setpoint (for the "Actuating drive speed" application)
C00011
Appl.: Reference speed Reference speed
C00012
Accel. time - main setpoint Acceleration time
C00013
Decel. time - main setpoint Deceleration time
C00015
VFC: V/f base frequency Base frequency
C00016
VFC: Vmin boost V
min
boost
C00022
Imax (motor mode) Current limit (in motor mode)
C00087
Rated motor speed Rated motor speed
C00089
Rated motor freq. Rated motor frequency
C00039/1
Fixed setpt 1 Fixed setpoint JOG1
C00727/3
bSetSpeedCcw Change of direction of rotation
C00727/4
bJogSpeed1 Jog value 1 for motor speed
C00051 MCTRL: Act. speed val. Current speed value
C00054 Motor curr. Motor current
Highlighted in grey = display parameter
SAVE