8400 HighLine | Parameter setting & configuration
Commissioning
Commissioning the "Actuating drive speed" TA using the »Engineer«
48 L Firmware 05.00 - DMS 4.2 EN - 02/2010
6. Set the reference speed
Change back to Application parameters tab.
In the Reference speed input field (C00011
), enter the reference speed of the motor.
The reference speed is indicated on the motor nameplate.
Tip!
Also check the other information on the nameplate against the motor data set in
the drive controller. You can find further information in the section entitled "Motor
selection/Motor data". ( 97)
7. Parameterise technology application
Open the Application Parameters tab and adapt the setting parameters of the
technology application according to the purpose it is to be used for.
Short overview of the most important setting parameters:
8. Optional: Change I/O connection (e.g. terminal assignment)
Possibility 1
: Change control mode in the Control mode list field (C00007).
The corresponding wiring diagram is displayed in a pop-up window if you click the
button right to the list field.
For a detailed description, see chapter entitled "Terminal assignment of the control
modes". ( 274)
Option 2
: Use the configuration parameters of the technology application to change
the I/O connection preconfigured in the selected control mode.
For a short overview, see chapter entitled "Configuration parameters (short
overview)". ( 289)
Option 3
: Change the I/O connection in the FB editor on the I/O interconnection level.
9. Save parameters and test application
Save parameter set.
Enable drive controller: Set X5/RFR terminal to HIGH level or close contact (see block
diagram [3-2]
).
The speed can be changed with the setpoint potentiometer ("R", see block diagram [3-
2]).
Parameter Info Lenze setting
Value Unit
C00012 Accel. time - main setpoint 2.000 s
C00013
Decel. time - main setpoint 2.000 s
C00105
Deceleration time - quick stop 2.000 s
C00039/1
Fixed setpoint 1 40.00 %
C00039/2
Fixed setpoint 2 60.00 %
C00039/3
Fixed setpoint 3 80.00 %
efesotomasyon.com - Lenze