EasyManua.ls Logo

Lenze E84AVHC Series - Page 943

Lenze E84AVHC Series
1118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware 05.00 - DMS 4.2 EN - 02/2010 L 943
8400 HighLine | Parameter setting & configuration
Function library
Function blocks | L_Curve_1
Exceptions
Step changes/discontinuities can be displayed by using the same parameter setting for
two consecutive X values. A step change is only valid if it has a valid pair of variates.
Otherwise, extrapolation continues, starting at the last valid pair of variates.
[14-23] Example: Characteristic with step change
If only one interpolation point, x1, in the negative range is defined, x2 exists with the
"0 %" Lenze setting being the valid interpolation point (x2 > x1), and a line is drawn
through both interpolation points:
[14-24] Example: Characteristic with only one defined interpolation point and x1 < 0
1 2 3 4 5 6 7 ... 32
X
-130 % -70 % -70 % 80 % 0 % 0 % 0 % 0 % 0 %
y(x)
-150 % -75 % 85 % 160 % 0 % 0 % 0 % 0 % 0 %
nOut_a
nIn_a
x1, y1
x3, y3
x4, y4
-199.99 % / -199.99 %
199.99 % / 199.99 %
x2, y2
1 2 3 4 5 6 7 8 9
X
-130 % 0 %0 %0 %0 %0 %0 %0 %0 %
y(x)
40 % 0 %0 %0 %0 %0 %0 %0 %0 %
nOut_a
nIn_a
x1, y1 x2, y2
-199.99 % / -199.99 %
199.99 % / 199.99 %
efesotomasyon.com - Lenze