8400 HighLine | Parameter setting & configuration
Commissioning
Commissioning the "Switch-off positioning" TA using »Engineer«
62 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
 
3. Start the »Engineer« & establish online connection to drive controller
 Follow the menu navigation in the Start-up wizard. Various options regarding the next 
steps to be taken are offered in the wizard.
– For example, the option "Do you want to open an existing Engineer project?", which 
appears at the beginning. You specify the next steps to be taken by answering Yes or 
No.
 Add the corresponding components from the catalogue to the project:
– Drive controller 8400 HighLine C
– Communication module
– Application
–Motor
 Select the drive controller in the Project view.
 Go online.
4. Load the Lenze setting
In order to achieve a defined device configuration, it is advisable to make sure that the
device is in its original delivery state.
 In the workspace, change to the All parameters tab.
 Set a value of "1: On / start" for code C00002/1
 in the parameter list.
– After the Lenze setting has been loaded, the "Actuating drive speed" TA has been 
preset with the "Terminals 0
" control mode.
5. Check the firmware
It is advisable to check the software version (firmware version), especially if an older drive
controller is being used (e.g. one kept in storage by the customer).
 All information that only applies to a certain controller software version or higher is 
identified accordingly in this documentation.
 The software version of the device can be found
– in the line "SW" on the nameplate
– by reading out code C00099
 (firmware version)
6. Set the reference speed
 Change back to Application parameters tab.
 In the Reference speed input field (C00011
), enter the reference speed of the motor. 
The reference speed is indicated on the motor nameplate.