Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 63
8400 HighLine | Parameter setting & configuration
Commissioning
Commissioning the "Switch-off positioning" TA using »Engineer«
 
7. Parameterise technology application
 Go to the "Application Parameters" tab and select the technology application "Switch-
off positioning", C00005 (= 3000)
. The contents of the tab are then adapted to the set 
application.
 Select the control mode appropriate to the application.
–The control mode (C00007
) is used to determine the source from which the 
application is to be controlled and how the digital and analog inputs are outputs are 
preset.
– In this example, switch-off positioning with
 feedforward control is described. The 
appropriate control mode Terminals 11
  is selected and has been wired according to 
the block diagram [3-4]
 .
8. Optional: Change I/O connection (e.g. terminal assignment)
 Possibility 1
: Change control mode in the Control mode list field (C00007).
– The corresponding wiring diagram is displayed in a pop-up window if you click the 
 button right to the list field.
– For a detailed description, see chapter entitled "Terminal assignment of the control 
modes". ( 274) 
 Option 2
: Use the configuration parameters of the technology application to change 
the I/O connection preconfigured in the selected control mode.
– For a short overview, see chapter entitled "Configuration parameters (short 
overview)". ( 289) 
 Option 3
: Change the I/O connection in the FB editor on the  I/O interconnection level.