HTU Control Registers
www.ti.com
1164
SPNU563A–March 2018
Submit Documentation Feedback
Copyright © 2018, Texas Instruments Incorporated
High-End Timer Transfer Unit (HTU) Module
24.4.18 Memory Protection 1 Start Address Register (HTU MP1S)
This register configures the start address of memory protection region 1.
Figure 24-31. Memory Protection 1 Start Address Register (HTU MP1S) [offset = 4Ch]
31 16
STARTADDRESS1
R/WP-0
15 2 1 0
STARTADDRESS1 0 0
R/WP-0
LEGEND: R/W = Read/Write; WP = Write in privilege mode only; -n = value after reset
Table 24-31. Memory Protection 1 Start Address Register (HTU MP1S) Field Descriptions
Bit Field Description
31-0 STARTADDRESS1 The start address defines at which main memory address the region begins. A memory protection error
will be triggered, if the HTU accesses an address smaller than STARTADDRESS1 and the MPCS bit
REG01ENA register is configured accordingly. The address is 32-bit aligned, so the 2 LSBs are not
significant and will always read 0.
24.4.19 Memory Protection 1 End Address Register (HTU MP1E)
Figure 24-32. Memory Protection 1 End Address Register (HTU MP1E) [offset = 50h]
31 16
ENDADDRESS1
R/WP-0
15 2 1 0
ENDADDRESS1 0 0
R/WP-0
LEGEND: R/W = Read/Write; WP = Write in privilege mode only; -n = value after reset
Table 24-32. Memory Protection 1 End Address Register (HTU MP1E) Field Descriptions
Bit Field Description
31-0 ENDADDRESS1 The end address defines at which address the region ends. A memory protection error will be
triggered, if the HTU accesses an address bigger than ENDADDRESS1 and the register bit
REG01ENA is configured accordingly. The address is 32-bit aligned, so the 2 LSBs are not significant
and will always read 0. The effective end address is rounded up to the nearest word end address, that
is, 0x200 = 0x203.