744 Keysight InfiniiVision 3000T X-Series Oscilloscopes Programmer's Guide
29 :SBUS<n> Commands
:SBUS<n>:CAN:TRIGger:PATTern:ID:MODE
(see page 1276)
Command Syntax
:SBUS<n>:CAN:TRIGger:PATTern:ID:MODE <value>
<value> ::= {STANdard | EXTended}
The :SBUS<n>:CAN:TRIGger:PATTern:ID:MODE command sets the CAN identifier
mode. STANdard selects the standard 11-bit identifier. EXTended selects the
extended 29-bit identifier. The CAN identifier is set by the
:SBUS<n>:CAN:TRIGger:PATTern:ID command.
Query Syntax
:SBUS<n>:CAN:TRIGger:PATTern:ID:MODE?
The :SBUS<n>:CAN:TRIGger:PATTern:ID:MODE? query returns the current setting
of the CAN identifier mode.
Return Format
<value><NL>
<value> ::= {STAN | EXT}