3.5 PoE
SCALANCE XM-400/XR-500 Command Line Interface (CLI)
132 Configuration Manual, 06/2016, C79000-G8976-C252-11
poe pse <integer (1-4)> usage <integer (1-100)>
The parameters have the following meaning:
Parameter
Description
Range of values / note
integer
Number of the PSE
1 … 4
integer
Value for "Usage Threshold" as a
percentage.
1 ... 100
Default: 80%
Result
The value for "Usage Threshold" is configured.
3.5.2.4
no poe pse usage
Description
With this command, you reset the parameter "Usage Threshold" to the default value.
Requirement
You are in the Global configuration mode.
The command prompt is as follows:
cli(config)#
Syntax
Call up the command with the following parameters:
no poe pse <integer (1-4)> usage
The parameter has the following meaning:
Parameter
Description
Range of values / note
integer
Number of the PSE
1 … 4
Result
The parameter "Usage Threshold" is reset to the default value.

Table of Contents

Other manuals for Siemens SCALANCE XM-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE XM-400 and is the answer not in the manual?

Siemens SCALANCE XM-400 Specifications

General IconGeneral
BrandSiemens
ModelSCALANCE XM-400
CategorySwitch
LanguageEnglish

Related product manuals