Diagnostics
12.2 FMP
SCALANCE XM-400/XR-500 Command Line Interface (CLI)
910 Configuration Manual, 06/2016, C79000-G8976-C252-11
Syntax
Call up the command with the following parameters:
rmon rx-power [req]<1/10 dBm> [dem]<1/10 dBm>
The parameters have the following meaning:
Parameter
Description
Range of values / note
req
Specify the value at which you are informed of
the deterioration of the received power by a
message of the severity level "Warning"
0 ... -40 dB
The default value depends on the rele-
vant pluggable transceiver.
dem
Specify the value at which you are informed of
the deterioration of the received power by a
message of the severity level "Critical"
0 ... -40 dB
The default value depends on the rele-
vant pluggable transceiver.
Result
The limits for monitoring the received power are defined.
Further notes
You enable this function with the fmp command.
You disable this function with the
no fmp command.
You display the status of this function and other information with the
show fmp stauts and
show fmp limit commands.
You define the limit values for the power loss with the command
fmp power-loss.