Command Manual – PoE 
Quidway S8500 Series Routing Switches  Chapter 2  PoE PSU Supervision Commands
 
Huawei Technologies Proprietary 
2-6 
2.2  PoE PSU Supervision Configuration Commands 
2.2.1  poe-power input-thresh lower 
Syntax 
poe-power input-thresh lower string 
View 
System view 
Parameter 
string: Undervoltage alarm threshold. It ranges from 90.00 V to 264.00 V in the format 
of X.X and within the accuracy of the second decimal. 
Description 
Use the poe-power input-thresh lower command to set the undervoltage alarm 
threshold of AC input for the PoE PSUs (lower threshold): 
z  For 220 VAC input, it is recommended to set the threshold to 181.0 V. 
z  For 110 VAC input, it is recommended to set the threshold to 90.0 V. 
Example 
# Set the undervoltage alarm threshold of AC input to 181.0 V. 
[Quidway] poe-power input-thresh lower 181.0 
Set lower input-threshold power successfully! 
2.2.2  poe-power input-thresh upper 
Syntax 
poe-power input-thresh upper string 
View 
System view 
Parameter 
string: Overvoltage alarm threshold. It ranges from 90 V to 264 V in the format of X.X. 
Description 
Use the poe-power input-thresh upper command to set overvoltage alarm threshold 
of AC input (upper threshold): 
z  For 220 VAC input, it is recommended to set the threshold to 264.0 V. 
z  For 110 VAC input, it is recommended to set the threshold to 132.0 V.