Faults and alarms
List of faults and alarms
3-1002
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Remedy: - re-configure the drive belonging to the Sensor Module in the commissioning software project (encoder configura-
tion) and download the new configuration to the drive unit.
- delete the drive belonging to the Sensor Module in the commissioning software project and download the new con-
figuration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check the 24 V supply voltage.
- check that the Sensor Module is working properly.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
A01483 Topology: Comparison Terminal Module missing in the actual topology
Message value: Component number: %1
Drive object: CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a Terminal Module in the target topology that is not available in the actual
topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy: - delete the Terminal Module in the commissioning software project and download the new configuration to the drive
unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check the 24 V supply voltage.
- check that the Terminal Module is working properly.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
A01484 Topology: Comparison DRIVE-CLiQ Hub Module missing in the actual topology
Message value: Component number: %1
Drive object: CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a DRIVE-CLiQ Hub Module in the target topology that does not exist in the
actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy: - delete the DRIVE-CLiQ Hub Module in the commissioning software project and download the new configuration to
the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check the 24 V supply voltage.
- test the DRIVE-CLiQ Hub Module to ensure that it functions properly.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
A01486 Topology: Comparison DRIVE-CLiQ components missing in the actual topology
Message value: Component number: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a DRIVE-CLiQ component in the target topology that is not available in the
actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.